O: Operator-Related Settings; O1: Digital Operator Display Selection - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.11 o: Operator-Related Settings
B.11 o: Operator-Related Settings
The o parameters set up the digital operator displays.
u

o1: Digital Operator Display Selection

No.
(Addr.
Name
Hex)
o1-01
Drive Mode Unit Monitor
(500)
Selection
o1-02
User Monitor Selection after
(501)
Power Up
o1-03
Digital Operator Display
(502)
Selection
o1-05
(0504)
LCD Contrast Control
<2>
o1-06
User Monitor Selection
(517)
Mode
o1-07
Second Line Monitor
(518)
Selection
o1-08
Third Line Monitor
(519)
Selection
o1-09
Frequency Reference
(51C)
Display Units
o1-10
User-Set Display Units
(520)
Maximum Value
o1-11
User-Set Display Units
(521)
Decimal Display
Frequency Reference and
o1-13
Frequency Related Monitor
(3105)
Custom Units 1
470
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: Uo-oo.
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04)
3: User-selected units (set by o1-09, o1-10 and o1-11)
Sets the contrast of the LCD operator.
Selects the monitors displayed on the second and third lines of the digital
operator display.
0: 3 Monitor Sequential (displays the next two sequential monitors)
1: 3 Monitor Selectable (set by o1-07 and o1-08)
Selects the monitor that is shown in the second line.
Enter the last three digits of the monitor parameter number to be displayed:
Uo-oo. For example, set "403" to display monitor parameter U4-03.
Note:
Parameter is effective only when o1-06 is set to 1.
Selects the monitor that is shown in the third line.
Enter the last three digits of the monitor parameter number to be displayed:
Uo-oo. For example, set "403" to display monitor parameter U4-03.
Note:
Parameter is effective only when o1-06 is set to 1.
Sets unit display for the frequency reference parameters and frequency related
monitors when o1-03 = 3.
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second)
8: Bar (Bar)
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: "Hg (inches of mercury)
24: Custom units (determined by o1-13 to o1-15)
25: None
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Sets the first character of the customer-specified unit display when o1-03 is
set to 3 and o1-09 is set to 24.
Description
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Values
Page
Default: 106
(Monitor U1-06)
267
Range: 104 to 809
Default: 1
267
Range: 1 to 5
Default: 0
267
Range: 0 to 3
Default: 3
Min.: 0
268
Max.: 5
Default: 0
267
Range: 0, 1
Default: 102
267
Range: 101 to 799
Default: 103
267
Range: 101 to 799
Default: 25
Range: 0 to 15; 24,
267
25
<1>
Default:
269
Range: 1 to 60000
<1>
Default:
269
Range: 0 to 3
Default: 41
269
Range: 30 to 7A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents