5.5 E: Motor Parameters
n
E2-03: Motor No-Load Current
Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive sets
E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load current
listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of the
motor test report.
No.
E2-03
Note:
The number of decimal places in the parameter value depends on the drive model 1. This value has two decimal places (0.01 A) if the drive
is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor
capacity is higher than 11 kW.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
E2-04
n
E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is automatically
calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it manually.
When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.
No.
E2-05
<1>
n
E2-06: Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. This value is automatically set
during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
No.
E2-06
n
E2-10: Motor Iron Loss for Torque Compensation
Sets the motor iron loss in watts.
No.
E2-10
n
E2-11: Motor Rated Power
Sets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be
saved to E2-11.
No.
E2-11
196
Parameter Name
Motor No-Load Current
Refer to Power Ratings on page 394
Parameter Name
Number of Motor Poles
Parameter Name
Motor Line-to-Line Resistance
Parameter Name
Motor Leakage Inductance
Parameter Name
Motor Iron Loss for Torque Compensation
Parameter Name
Motor Rated Power
Setting Range
0 to [E2-01]
(unit: 0.01 A)
for details.
Setting Range
2 to 48
Setting Range
0.000 to 65.000 mΩ
Setting Range
0.0 to 40.0%
Setting Range
0 to 65535 W
Setting Range
0.00 to 650.00 kW
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
Determined by
o2-04
Default
4
Default
Determined by
<1>
o2-04
Default
Determined by
o2-04
Default
Determined by
o2-04
Default
Determined by
o2-04