YASKAWA P1000 Technical Manual page 459

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
H3-03
(411)
Terminal A1 Gain Setting
H3-04
(412)
Terminal A1 Bias Setting
H3-05
Terminal A3 Signal Level
(413)
Selection
H3-06
Terminal A3 Function
(414)
Selection
H3-07
(415)
Terminal A3 Gain Setting
H3-08
(416)
Terminal A3 Bias Setting
H3-09
Terminal A2 Signal Level
(417)
Selection
H3-10
Terminal A2 Function
(418)
Selection
H3-11
(419)
Terminal A2 Gain Setting
H3-12
(41A)
Terminal A2 Bias Setting
H3-13
Analog Input Filter Time
(41B)
Constant
H3-14
Analog Input Terminal
(41C)
Enable Selection
H3-16
Terminal A1 Offset
(2F0)
H3-17
Terminal A2 Offset
(2F1)
H3-18
Terminal A3 Offset
(2F2)
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Description
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
Sets the level of the input value selected in H3-02 when 0 V is input at terminal
A1.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use Jumper S1 to set input terminal A3 for a current or voltage
input signal.
Sets the function of terminal A3.
Sets the level of the input value selected in H3-06 when 10 V is input at
terminal A3.
Sets the level of the input value selected in H3-06 when 0 V is input at terminal
A3.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use Jumper S1 to set input terminal A2 for a current or voltage
input signal.
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input
at terminal A2.
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used
for noise filtering.
Determines which analog input terminals will be enabled when a digital input
programmed for "Analog input enable" (H1-oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Adds an offset when the analog signal to terminal A1 is at 0 V.
Adds an offset when the analog signal to terminal A2 is at 0 V.
Adds an offset when the analog signal to terminal A3 is at 0 V.
B.8 H Parameters: Multi-Function Terminals
Values
Page
Default: 100.0%
Min.: -999.9
225
Max.: 999.9
Default: 0.0%
Min.: -999.9
225
Max.: 999.9
Default: 0
226
Range: 0 to 3
Default: 2
226
Range: 0 to 26
Default: 100.0%
Min.: -999.9
226
Max.: 999.9
Default: 0.0%
Min.: -999.9
226
Max.: 999.9
Default: 2
226
Range: 0 to 3
Default: 0
227
Range: 0 to 26
Default: 100.0%
Min.: -999.9
227
Max.: 999.9
Default: 0.0%
Min.: -999.9
227
Max.: 999.9
Default: 0.03 s
Min.: 0.00
227
Max.: 2.00
Default: 7
227
Range: 1 to 7
Default: 0
Min.: -500
227
Max.: 500
Default: 0
Min.: -500
227
Max.: 500
Default: 0
Min.: -500
227
Max.: 500
459