B.8 H Parameters: Multi-Function Terminals
H2-oo
Function
Setting
1E
Restart enabled
1F
Motor overload alarm (oL1)
20
Drive overheat pre-alarm (oH)
Mechanical weakening
22
detection
2F
Maintenance period
37
During frequency output
38
Drive enabled
39
Watt hour pulse output
3C
LOCAL/REMOTE status
3D
During speed search
3E
PID feedback low
3F
PID feedback high
4A
During KEB Ride-Thru
4C
During fast stop
4D
oH Pre-alarm time limit
4E
Braking transistor fault (rr)
4F
Braking resistor overheat (oH) Closed: The dynamic braking resistor has overheated.
50
Waiting to Run
51
Sequence timer 1
52
Sequence timer 2
53
Sequence timer 3
54
Sequence timer 4
58
Underload detection
60
Internal cooling fan alarm
71
Secondary PI Feedback Low
72
Secondary PI Feedback High Closed: The PI2 feedback level is too high.
89
Output I Lim
<1>
100 to 189 Function 0 to 89 with inverse
output
<1> Available in drive software versions PRG: 8503 and later.
u

H3: Multi-Function Analog Inputs

No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal Level
(410)
Selection
H3-02
Terminal A1 Function
(434)
Selection
458
H2 Multi-Function Digital Output Settings
Closed: An automatic restart is performed
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
Closed: The heatsink temperature exceeds the L8-02 level (while L8-03 = 3 or 4), or an external
device has triggered an oH2 alarm via multi-function input H1-oo = B.
Closed: Mechanical weakening detected.
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require
maintenance.
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
Closed: Multi-function input set for "Drive enable" is closed (H1-oo = 6A)
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
Open: REMOTE
Closed: LOCAL
Closed: Speed Search is being executed.
Closed: PID feedback level is too low.
Closed: The PID feedback level is too high.
Closed: KEB Ride-Thru is being performed.
Closed: A Fast Stop command has been entered from the operator or input terminals.
Closed: An oH pre-alarm is present after 10 output frequency reduction cycles have passed (L8-03
= 4).
Closed: The built-in dynamic braking transistor failed.
Closed: b1-11 Timer is active.
Closed: Sequence timer 1 is active.
Closed: Sequence timer 2 is active.
Closed: Sequence timer 3 is active.
Closed: Sequence timer 4 is active.
Closed: Underload is detected.
Closed: Internal cooling fan alarm
Closed: PI2 feedback level is too low.
Closed: Drive output speed is being limited due to the output current limit or due the single-phase
foldback regulator.
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use Jumper S1 to set input terminal A1 for a current or voltage
input signal.
Sets the function of terminal A1.
Description
Description
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Page
222
222
222
222
222
222
223
223
223
223
223
223
223
223
223
223
223
223
223
223
223
223
223
224
224
224
224
224
Values
Page
Default: 0
225
Range: 0 to 3
Default: 0
225
Range: 0 to 26

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents