YASKAWA P1000 Technical Manual page 452

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.7 F: Communication Options
No.
(Addr.
Name
Hex)
F7-18
EtherNet/IP Current Scaling
(3F6)
Factor
F7-19
EtherNet/IP Torque Scaling
(3F7)
Factor
F7-20
EtherNet/IP Power Scaling
(3F8)
Factor
F7-21
EtherNet/IP Voltage Scaling
(3F9)
Factor
F7-22
EtherNet/IP Time Scaling
(3FA)
F7-23 to
F7-32
Dynamic Output Assembly
(3FB to
Parameters
374)
F7-33 to
F7-42
Dynamic Input Assembly
(375 to
Parameters
37E)
F7-60
(0780)
PZD1 Write
<1>
F7-61
(0781)
PZD2 Write
<1>
F7-62
(0782)
PZD3 Write
<1>
F7-63
(0783)
PZD4 Write
<1>
F7-64
(0784)
PZD5 Write
<1>
F7-65
(0785)
PZD6 Write
<1>
F7-66
(0786)
PZD7 Write
<1>
F7-67
(0787)
PZD8 Write
<1>
F7-68
(0788)
PZD9 Write
<1>
F7-69
(0789)
PZD10 Write
<1>
F7-70
(078A)
PZD1 Read
<1>
F7-71
(078B)
PZD2 Read
<1>
452
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID
2AH Object.
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly 116
will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus register.
Parameters used in Input Assembly 166. Each parameter contains a
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will be
read from this corresponding MEMOBUS/Modbus address. A MEMOBUS/
Modbus address value of 0 means that the value sent for Input Assembly 166
is not defined by the user, therefore the option default register value will be
returned.
Sets MEMOBUS/Modbus address for PZD1 Write (PPO Write).
Values 0 to 2 enable the PZD1 Write as STW.
Sets MEMOBUS/Modbus address for PZD2 Write (PPO Write).
Values 0 to 2 enable the PZD2 Write as HSW.
Sets MEMOBUS/Modbus address for PZD3 Write (PPO Write).
Values 0 to 2 disable the PZD3 Write.
Sets MEMOBUS/Modbus address for PZD4 Write (PPO Write).
Values 0 to 2 disable the PZD4 Write.
Sets MEMOBUS/Modbus address for PZD5 Write (PPO Write).
Values 0 to 2 disable the PZD5 Write.
Sets MEMOBUS/Modbus address for PZD6 Write (PPO Write).
Values 0 to 2 disable the PZD6 Write.
Sets MEMOBUS/Modbus address for PZD7 Write (PPO Write).
Values 0 to 2 disable the PZD7 Write.
Sets MEMOBUS/Modbus address for PZD8 Write (PPO Write).
Values 0 to 2 disable the PZD8 Write.
Sets MEMOBUS/Modbus address for PZD9 Write (PPO Write).
Values 0 to 2 disable the PZD9 Write.
Sets MEMOBUS/Modbus address for PZD10 Write (PPO Write).
Values 0 to 2 disable the PZD10 Write.
Sets MEMOBUS/Modbus address for PZD1 Read (PPO Read).
Values 0 to 2 enable the PZD1 Read as ZSW.
Sets MEMOBUS/Modbus address for PZD2 Read (PPO Read).
Values 0 to 2 enable the PZD2 Read as HIW.
Description
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Values
Page
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Default: 0
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF