B.12 S: Special Application
No.
(Addr.
Name
Hex)
S2-06
Sequence Timer 2 Start
(320B)
Time
S2-07
Sequence Timer 2 Stop Time
(320C)
S2-08
Sequence Timer 2 Day
(320D)
Selection
S2-09
Sequence Timer 2 Selection
(320E)
S2-10
Sequence Timer 2 Reference
(320F)
Source
S2-11
Sequence Timer 3 Start
(3210)
Time
S2-12
Sequence Timer 3 Stop Time
(3211)
S2-13
Sequence Timer 3 Day
(3212)
Selection
S2-14
Sequence Timer 3 Selection
(3213)
S2-15
Sequence Timer 3 Reference
(3214)
Source
S2-16
Sequence Timer 4 Start
(3215)
Time
474
Sets the start time for timer 2. The value must be set less than or equal to S2-07. Default: 00:00
Sets the stop time for timer 2. The value must be set greater than or equal to
S2-06.
Sets the days for which sequence timer 2 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the action that occurs when sequence timer 2 is active.
0: Digital output only
1: Run
2: Run - PI disable
Selects the frequency reference source used for running the drive when
sequence timer 2 is active (only applicable when S2-09 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
Sets the start time for timer 3. The value must be set less than or equal to S2-12. Default: 00:00
Sets the stop time for timer 3. The value must be set greater than or equal to
S2-11.
Sets the days for which sequence timer 3 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the action that occurs when sequence timer 3 is active.
0: Digital output only
1: Run
2: Run - PI disable
Selects the frequency reference source used for running the drive when
sequence timer 3 is active (only applicable when S2-14 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
Sets the start time for timer 4. The value must be set less than or equal to S2-17. Default: 00:00
Description
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Values
Page
Min.: 00:00
279
<1>
Max.: 24:00
Default: 00:00
Min.: 00:00
280
<1>
Max.: 24:00
Default: 0
280
Range: 0 to 10
Default: 0
280
Range: 0 to 2
Default: 0
281
Range: 0 to 7
Min.: 00:00
279
<1>
Max.: 24:00
Default: 00:00
Min.: 00:00
280
<1>
Max.: 24:00
Default: 0
280
Range: 0 to 10
Default: 0
280
Range: 0 to 2
Default: 0
281
Range: 0 to 7
Min.: 00:00
279
<1>
Max.: 24:00