1.10 o: Operator-Related Settings

These parameters control the various functions, features, and display of the HOA keypad.
u

o1: HOA Keypad Display Selection

These parameters determine the data display on the HOA keypad.
n
o1-01: Drive Mode Unit Monitor Selection
When o1-02 is set to 5, any U monitors can be displayed. This parameter will select the monitors. Pressing the up arrow key
will display the following data: frequency reference → rotational direction → output frequency → output current → o1-01
selection.
Parameter o1-01 selects the content of the last monitor in this sequence. This is done by entering the "1oo" part of
"U1-oo". Certain monitors are not available in some control modes. There is no effect like this on an LCD operator.
No.
o1-01
<1> U2-oo and U3-oo parameters cannot be selected.
n
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter is displayed upon power up by entering the 1- oo part of U1-oo. Certain monitors are
not available in some control modes.
No.
o1-02
<1> Default is 1 when b5-01 is set to 0.
Default is 3 when b5-01 is set to 1 or 3.
Setting 1: Frequency Reference (U1-01)
Setting 2: Motor Direction
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Monitor
The monitor value selected by o1-01 will be displayed.
n
o1-03: HOA Keypad Display Selection
Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units before setting
parameters o1-10 and o1-11.
No.
o1-03
Setting 0: 0.01 Hz Units
Setting 1: 0.01% Units (100% = Max Output Frequency)
Setting 2: r/min Units (Calculated by the Max Output Frequency and the Number of Motor Poles)
Setting 3: User-set Units (Use o1-10, o1-11)
Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number to
o1-11.
For example, to have the maximum output frequency displayed as "100.00", set o1-10 = 1000 and o1-11 = 2 (i.e., 1000 with
2 decimal points).
Note:
1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
U1-01: frequency reference
U1-02: output frequency
U1-16: output frequency after softstarter (accel/decel ramp generator)
d1-01 to d1-17: frequency references
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Name
Drive Mode Unit Monitor Selection
Refer to U: Monitor Parameters on page 164
Name
User Monitor Selection after Power Up
Name
HOA Keypad Display Selection

1.10 o: Operator-Related Settings

Setting Range
104 to 914
U1-04 (Control Mode) to
<1>
U9-14 (Power Monitor)
for a list of monitors.
Setting Range
1 to 5
Setting Range
0 to 3
Default
106 (U1-06)
Default
<1>
Default
0
1
133