B.5 d: References
No.
(Addr.
Name
Hex)
d1-17
(292)
Jog Frequency Reference
<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
u

d2: Frequency Upper/Lower Limits

No.
(Addr.
Name
Hex.)
d2-01
Frequency Reference Upper
(289)
Limit
d2-02
Frequency Reference Lower
(28A)
Limit
d2-03
Master Speed Reference
(293)
Lower Limit
u

d3: Jump Frequency

No.
(Addr.
Name
Hex)
d3-01
Jump Frequency 1
(294)
d3-02
Jump Frequency 2
(295)
d3-03
Jump Frequency 3
(296)
d3-04
Jump Frequency Width
(297)
u

d4: Frequency Reference Hold and Up/Down 2 Function

No.
(Addr.
Name
Hex)
d4-01
Frequency Reference Hold
(298)
Function Selection
d4-03
Frequency Reference Bias
(2AA)
Step (Up/Down 2)
d4-04
Frequency Reference Bias
(2AB)
Accel/Decel (Up/Down 2)
444
Sets the Jog frequency reference. Setting units are determined by parameter
o1-03.
Sets the frequency reference upper limit as a percentage of the maximum
output frequency.
Sets the frequency reference lower limit as a percentage of the maximum
output frequency.
Sets the lower limit for frequency references from analog inputs as a
percentage of the maximum output frequency.
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Eliminates problems with resonant vibration of the motor/machine by
avoiding continuous operation in predefined frequency ranges. The drive
accelerates and decelerates the motor through the prohibited frequency ranges.
Setting 0.0 disables this function.
Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.
Sets the dead-band width around each selected prohibited frequency reference
point.
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency that
was saved.
Sets the bias added to the frequency reference when the Up 2 and Down 2
digital inputs are enabled (H1-oo = 75, 76).
0: Use selected accel/decel time.
1: Use accel/decel time 4 (C1-07 and C1-08).
Note:
The functionality of setting 1 is only accessible via
MEMOBUS/Modbus communication.
Description
Description
Description
Description
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Values
Page
Default: 6.00 Hz
Min.: 0.00
182
<1>
Max.: 400.00
Setting
Page
Default: 100.0%
Min.: 0.0
184
Max.: 110.0
Default: 0.0%
Min.: 0.0
184
Max.: 110.0
Default: 0.0%
Min.: 0.0
185
Max.: 110.0
Values
Page
Default: 0.0 Hz
Min.: 0.0
185
Max.: 400.0
Default: 0.0 Hz
Min.: 0.0
185
Max.: 400.0
Default: 0.0 Hz
Min.: 0.0
185
Max.: 400.0
Default: 1.0 Hz
Min.: 0.0
185
Max.: 20.0
Values
Page
Default: 0
186
Range: 0, 1
Default: 0.00 Hz
Min.: 0.00
187
Max.: 99.99
Default: 0
188
Range: 0, 1