H4: Analog Outputs - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.8 H Parameters: Multi-Function Terminals
H3-oo
Function
Setting
0
Frequency bias
1
Frequency gain
2
Auxiliary frequency reference 1
3
Auxiliary frequency reference 2
4
Output voltage bias
5
Accel/decel time gain
6
DC Injection Braking current
Overtorque/undertorque
7
detection level
8
Stall Prevention level during run
9
Output frequency lower limit level
B
PID feedback
C
PID setpoint
D
Frequency bias
E
Motor Temperature (PTC Input)
16
Differential PID feedback
17
Motor Thermistor (NTC)
1F
Through mode
25
Secondary PI Setpoint
26
Secondary PI Feedback
u

H4: Analog Outputs

No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-01
Output Terminal FM
(41D)
Monitor Selection
H4-02
Multi-Function Analog
(41E)
Output Terminal FM Gain
H4-03
Multi-Function Analog
(41F)
Output Terminal FM Bias
Multi-Function Analog
H4-04
Output Terminal AM
(420)
Monitor Selection
H4-05
Multi-Function Analog
(421)
Output Terminal AM Gain
H4-06
Multi-Function Analog
(422)
Output Terminal AM Bias
Multi-Function Analog
H4-07
Output Terminal FM Signal
(423)
Level Selection
460
H3 Multi-Function Analog Input Settings
10 V = E1-04 (maximum output frequency)
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100
to 0%.
10 V = E1-04 (maximum output frequency)
10 V = E1-04 (maximum output frequency)
10 V = E1-05 (motor rated voltage)
10 V = 100%
10 V = Drive rated current
10 V = Drive rated current (V/f)
10 V = Drive rated current
10 V = E1-04 (maximum output frequency)
10 V = 100%
10 V = 100%
10 V = E1-04 (maximum output frequency)
10 V = 100%
Note:
A 12 kΩ resistor must be connected between one of the terminals A1, A2,
or A3 and V+ for PTC functionality. Connect the 12 kΩ resistor to the same
terminal as the PTC input. Do not connect terminals V+ to AC, or damage
to the drive may result.
10 V = 100%
10 V = -9 °C
0 V = 234 °C
Set this value when using the terminal in the pass-through mode.
10 V = S3-02 (maximum output frequency)
10 V = S3-02 (maximum output frequency)
Selects the data to be output through multi-function analog output terminal
FM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal FM that is equal to 100% of the selected
monitor value.
Sets the signal level at terminal FM that is equal to 0% of the selected monitor
value.
Selects the data to be output through multi-function analog output terminal
AM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal AM that is equal to 100% of the selected
monitor value.
Sets the signal level at terminal AM that is equal to 0% of the selected monitor
value.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20mA
Description
Description
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Page
228
228
228
228
228
228
229
229
229
229
229
229
229
230
230
230
230
230
230
Values
Page
Default: 102
230
Range: 000 to 999
Default: 100.0%
Min.: -999.9
230
Max.: 999.9
Default: 0.0%
Min.: -999.9
230
Max.: 999.9
Default: 103
230
Range: 000 to 999
Default: 50.0%
Min.: -999.9
230
Max.: 999.9
Default: 0.0%
Min.: -999.9
230
Max.: 999.9
Default: 0
231
Range: 0 to 2

Hide quick links: