D3: Jump Frequency - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

n
d2-03: Master Speed Reference Lower Limit
Sets a lower limit as a percentage of the maximum output frequency that will only affect a frequency reference entered from
the analog input terminals (A1, A2, or A3) as the master speed reference. This is unlike parameter d2-02, which affects all
frequency references regardless of their source.
Note:
When lower limits are set to both parameters d2-02 and d2-03, the drive uses the greater of those two values as the lower limit.
No.
d2-03
u

d3: Jump Frequency

n
d3-01 to d3-04: Jump Frequencies 1, 2, 3 and Jump Frequency Width
The Jump frequencies are frequency ranges at which the drive will not operate. The drive can be programmed with three
separate Jump frequencies to avoid operating at speeds that cause resonance in driven machinery. If the speed reference falls
within a Jump frequency dead band, the drive will clamp the frequency reference just below the dead band and only accelerate
past it when the frequency reference rises above the upper end of the dead band.
Setting parameters d3-01 through d3-03 to 0.0 Hz disables the Jump frequency function.
No.
d3-01
d3-02
d3-03
d3-04
Figure 5.29
shows the relationship between the Jump frequency and the output frequency.
Note:
1. The drive will use the active accel/decel time to pass through the specified dead band range, but will not allow continuous operation in
that range.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Internal frequency
reference
d2-01
Operating
range
d2-02
Figure 5.28 Frequency Reference: Upper and Lower Limits
Parameter Name
Master Speed Reference Lower Limit
Parameter Name
Jump Frequency 1
Jump Frequency 2
Jump Frequency 3
Jump Frequency Width
Frequency
Reference
Frequency
reference
decreases
Jump
Frequency 3
d3-03
Figure 5.29 Jump Frequency Operation
Frequency Reference Upper Limit
Frequency Reference Lower Limit
Set frequency reference
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Jump
Frequency 2
Frequency 1
d3-02
d3-01
5.4 d: Reference Settings
Setting Range
0.0 to 110.0%
Setting Range
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 20.0 Hz
Frequency
reference
increases
Output
Frequency
Default
0.0%
Default
0.0 Hz
0.0 Hz
0.0 Hz
1.0 Hz
5