5.10 o: Operator Related Settings

5.10 o: Operator Related Settings

These parameters are for controlling the various functions, features, and display of the digital operator.

◆ o1: Digital Operator Display Selection

These parameters determine how data appears on the operator display.
o1-01: Drive Mode Unit Monitor Selection
When the drive is powered up, the monitor selected in parameter o1-02 appears first on the display. If o1-02 is set to 5,
o1-01 can be used to change the content of this monitor.
When using an LED operator, pressing the up arrow key will display the following data: speed reference → rotational
direction → output speed → output current → o1-01 selection.
Parameter o1-01 lets the user select the content of the last monitor in this sequence. There is no effect like this on an LCD
operator.
No.
o1-01
<1> U2- and U3- parameters cannot be selected.
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter is displayed upon power up. This is done by entering the 1 part of U1-. Certain
monitors are not available in some control modes.
No.
o1-02
Setting 1: Frequency reference (U1-01)
Setting 2: Motor direction
Setting 3: Output frequency (U1-02)
Setting 4: Output current (U1-03)
Setting 5: User-selected monitor (set by o1-01)
o1-03: Digital Operator Display Selection
Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units, then set
parameters o1-10 and o1-11.
No.
o1-03
Setting 0: 0.01 Hz units
Setting 1: 0.01% units (100% = max. output frequency)
Setting 2: r/min units (calculated by the max output frequency and the no. of motor poles)
Setting 3: User-set units (use o1-10, o1-11)
Set the value use for the maximum frequency reference to o1-10. The placement of the decimal point in this number
should be set to o1-11.
For example, to have the maximum output frequency displayed as "100.00", set the o1-10 = 1000 and o1-11 = 2 (i.e.,
1000 with 2 decimal points).
Note: 1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
 U1-01: frequency reference
 U1-02: output frequency
 U1-16: output frequency after softstarter (accel/decel ramp generator)
 d1-01 to d1-17: frequency references
2. Setting o1-03 to 2 requires that the number of motor poles be entered to E2-04 and E5-04.
246
Name
Drive Mode Unit Monitor Selection
Refer to U: Monitor Parameters on page 253
Name
User Monitor Selection after Power Up
Name
Digital Operator Display Selection
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Setting Range
105 to 825
U1-05 (Motor Speed) to U8-25(DWEZ
Custom Monitor 25)
<1>
for a list of monitors.
Setting Range
1 to 5
Setting Range
0 to 3
Default
106 (U1-06)
Default
1
Default
0