O4: Maintenance Monitor Settings - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

B.11 o: Operator-Related Settings
u

o4: Maintenance Monitor Settings

No.
(Addr.
Name
Hex)
o4-01
Cumulative Operation Time
(50B)
Setting
o4-02
Cumulative Operation Time
(50C)
Selection
o4-03
Cooling Fan Operation Time
(50E)
Setting
o4-05
Capacitor Maintenance
(51D)
Setting
o4-07
DC Bus Pre-Charge Relay
(523)
Maintenance Setting
o4-09
IGBT Maintenance Setting
(525)
o4-11
U2, U3 Initialization
(510)
o4-12
kWh Monitor Initialization
(512)
o4-13
Number of Run Commands
(528)
Counter Initialization
o4-17
Set/Reset Real-Time Clock
(3100)
o4-20
Time Display Format
(81F)
472
Sets the value for the cumulative operation time of the drive in units of 10 h. Default: 0
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.
Sets the value of the Maintenance Monitor for the soft charge bypass relay.
See U4-06 to check when the bypass relay may need to be replaced.
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 for IGBT
replacement times.
0: U2-oo and U3-oo monitor data is not reset when the drive is initialized
(A1-03).
1: U2-oo and U3-oo monitor data is reset when the drive is initialized
(A1-03).
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized
(A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).
0: Number of Run commands counter is not reset when the drive is initialized
(A1-03).
1: Number of Run commands counter is reset when the drive is initialized
(A1-03).
Sets the current date and time for the Real-Time Clock.
0: - -
1: Set
2: Reset
Sets the time display format.
0: 12-hour
1: 24-hour
Description
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Values
Page
Min.: 0
272
Max.: 9999
Default: 0
273
Range: 0, 1
Default: 0
Min.: 0
273
Max.: 9999
Default: 0%
Min.: 0
273
Max.: 150
Default: 0%
Min.: 0
273
Max.: 150
Default: 0%
Min.: 0
273
Max.: 150
Default: 0
273
Range: 0, 1
Default: 0
274
Range: 0, 1
Default: 0
274
Range: 0, 1
Default: 0
116
Range: 0 to 2
Default: 0
274
Range: 0, 1