<1> Refer to local codes while selecting wire size for terminals ⊖, ⊕1, ⊕2 if these terminals need to be used for other optional power devices.
<2> The wire size recommended for terminal ⊖, ⊕1, ⊕2 is for DC type additional impedance only. See the additional impedance type recommended
before choosing wire size for terminals ⊖, ⊕1, ⊕2.
in
Table A.14
<3> Terminal wire range is the range of wire sizes the terminals can accept. This information is intended to keep within the wire range of the terminals
while selecting a wire size for the terminals per local codes for the intended application of these terminals.
Table A.18 600 V Single-Phase Main Circuit Wiring and Tightening Torques
Drive Model
Terminal
R/L1, S/L2
5o0003
U/T1, V/T2, W/T3
5o0004
⊖, ⊕1, ⊕2
5o0006
5o0009
B1, B2
GND
R/L1, S/L2
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5o0011
B1, B2
GND
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual