D4: Frequency Reference Hold And Up/Down 2 Function - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

5.4 d: Reference Settings
2. When setting more than one Jump frequency, make sure that the parameters do not overlap.
u

d4: Frequency Reference Hold and Up/Down 2 Function

n
d4-01: Frequency Reference Hold Function Selection
Determines whether the frequency reference or the frequency bias (Up/Down 2) value is saved when the Stop command is
entered or the power supply is shut down. This parameter is effective when either of the digital input functions listed below
are used:
• Accel/decel ramp hold function (H1-oo= A)
• Up/Down function (H1-oo = 10 and 11)
• Up/Down 2 function (H1-oo = 75 and 76)
No.
d4-01
The operation depends on the function used with parameter d4-01.
Setting 0: Disabled
• Acceleration hold
The hold value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off. The active
frequency reference will be the value the drive uses when it restarts.
• Up/Down
The frequency reference value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off.
The drive will start from 0 Hz when it is restarted.
• Up/Down 2
The frequency bias is not saved when the Stop command is entered, or 5 s after the Up/Down 2 command has been released.
The Up/Down 2 function will start with a bias of 0% when the drive is restarted.
Setting 1: Enabled
• Acceleration hold
The last hold value will be saved when the Run command or the drive power is switched off and the drive will use the saved
value as the frequency reference when it restarts. Make sure to continuously enable the multi-function input terminal set for
"Accel/decel ramp hold" (H1-oo = A) or the hold value will be cleared when the power is switched on.
• Up/Down
The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will use
the frequency reference that was saved when it restarts.
• Up/Down 2 with frequency reference from digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the Up/Down 2 bias value is
added to the frequency reference and then reset to 0. This new frequency reference is saved and will also be used to restart
the drive after the power is cycled.
186
Parameter Name
Frequency Reference Hold Function Selection
Power supply
OFF
ON
Forward Run / Stop
OFF
ON
Hold Accel/Decel
Frequency reference
Output frequency
Hold
Figure 5.30 Frequency Reference Hold with Accel/Decel Hold Function
ON
ON
OFF
OFF
OFF
ON
Hold
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Setting Range
0, 1
ON
d4-01 = 1
d4-01 = 0
Default
0