YASKAWA P1000 Technical Manual page 192

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

5.5 E: Motor Parameters
Setting
0
1
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Variable torque 1
5
50 Hz, Variable torque 2
6
60 Hz, Variable torque 1
7
60 Hz, Variable torque 2
8
50 Hz, mid starting torque
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
F
<1>
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 2A0004 to 2A0021, 4A0002 to 4A0011, and 5A0003 to 5A0009
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V drives.
Setting = 0
50 Hz
200
15
9
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
200
35
8
0
1.3
25
50
Frequency (Hz)
Setting = 8
50 Hz
200
19
11
0
1.3 2.5
50
Frequency (Hz)
192
Table 5.16 Predefined V/f Patterns
Specification
50 Hz
60 Hz
60 Hz
Table 5.17 Constant Torque Characteristics, Settings 0 to 3
Setting = 1
200
15
9
0
1.5 3
Frequency (Hz)
Table 5.18 Derated Torque Characteristics, Settings 4 to 7
Setting = 5
200
50
9
0
1.3
Frequency (Hz)
Table 5.19 High Starting Torque, Settings 8 to B
Setting = 9
200
24
13
0
1.3 2.5
Frequency (Hz)
Characteristic
Constant torque
Variable torque
High starting torque
Constant output
Constant torque
60 Hz
Setting = 2
200
15
9
60
0
50 Hz
Setting = 6
200
35
8
0
25
50
50 Hz
Setting = A
200
19
11
50
0
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Application
For general purpose applications. Torque remains
constant regardless of changes to speed.
For fans, pumps, and other applications where the
required torque changes as a function of the speed.
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
Output voltage is constant when operating at greater than
60 Hz.
For general purpose applications. Torque remains
constant regardless of changes to speed.
60 Hz
Setting = 3
1.5 3
50
60
Frequency (Hz)
60 Hz
Setting = 7
1.5
30
60
Frequency (Hz)
60 Hz
Setting = B
1.5 3
60
Frequency (Hz)
72 Hz
200
15
9
0
1.5 3
60
72
Frequency (Hz)
60 Hz
200
50
9
0
1.5
30
60
Frequency (Hz)
60 Hz
200
24
15
0
1.5 3
60
Frequency (Hz)