H5: MEMOBUS/Modbus Serial Communication

No.
(Addr.
Name
Hex)
H5-01
(425)
Drive Node Address
<1>
H5-02
Communication Speed
(426)
Selection
H5-03
Communication Parity
(427)
Selection
H5-04
Stopping Method after
(428)
Communication Error (CE)
H5-05
Communication Fault
(429)
Detection Selection
H5-06
Drive Transmit Wait Time
(42A)
H5-07
RTS Control Selection
(42B)
H5-09
CE Detection Time
(435)
Unit Selection for
H5-10
MEMOBUS/Modbus
(436)
Register 0025H
H5-11
Communications ENTER
(43C)
Function Selection
H5-12
Run Command Method
(43D)
Selection
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
u

H6: Pulse Train Input

No.
(Addr.
Name
Hex)
H6-01
Pulse Train Input Terminal
(42C)
RP Function Selection
H6-02
(42D)
Pulse Train Input Scaling
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Description
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Description
Selects drive station node number (address) for MEMOBUS/Modbus
terminals R+, R-, S+, S-. Cycle power for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault
will occur.
Set the wait time between receiving and sending data.
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Sets the time required to detect a communications error.
Adjustment may be needed when networking several drives.
0: 0.1 V units
1: 1 V units
0: Drive requires an Enter command before accepting any changes to
parameter settings.
1: Parameter changes are activated immediately without the Enter command.
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
Description
0: Frequency reference
1: PID feedback value
2: PID setpoint value
Sets the terminal RP input signal frequency that is equal to 100% of the value
selected in H6-01.
B.8 H Parameters: Multi-Function Terminals
Values
Page
Default: 0
231
Range: 0 to 2
Values
Page
Default: 1F (Hex)
Min.: 0
511
Max.: FF
Default: 3
511
Range: 0 to 8
Default: 0
511
Range: 0 to 2
Default: 3
511
Range: 0 to 3
Default: 1
511
Range: 0, 1
Default: 5 ms
Min.: 5
512
Max.: 65
Default: 1
512
Range: 0, 1
Default: 2.0 s
Min.: 0.0
512
Max.: 10.0
Default: 0
512
Range: 0, 1
Default: 0
513
Range: 0, 1
Default: 0
513
Range: 0, 1
Values
Page
Default: 0
232
Range: 0 to 2
Default: 1440 Hz
Min.: 100
232
Max.: 32000
461