Emc Guidelines Compliance - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

D.2 European Standards
Drive Model
<1>
5A0062
<1>
5A0077
<1>
5A0099
<1>
5A0125
<1>
5A0145
<1>
5A0192
<1>
5A0242
<1> 600 V class drives are not compliant with European Standards.
n
Guarding Against Harmful Materials
When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive
from above or below.
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your Yaskawa representative for instructions.
u

EMC Guidelines Compliance

This drive is tested according to European standards IEC/EN 61800-3: 2004.
n
EMC Filter Installation
The following conditions must be met to ensure continued compliance with guidelines.
547
for EMC filter selection.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive
also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
A – Drive
B – 10 m max cable length between
C – Motor
5.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
544
Model
FWP-250A
FWP-250A
FWP-250A
FWP-350A
FWP-350A
FWP-600A
FWP-600A
A
drive and motor
Figure D.2 Installation Method
Fuse Type
Manufacturer: Bussmann
B
C
D
U/T1
U
V/T2
V
M
W/T3
W
E
D – Metal conduit
E – Ground wire should be as short as
possible.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Fuse Ampere Rating (A)
250
250
250
350
350
600
600
Refer to EMC Filters on page