Figure 5.21
illustrates how the Dwell function works.
Note:
Set the stopping method to "Ramp to Stop" (b1-03 = 0) to use the Dwell function.
n
b6-01, b6-02: Dwell Reference, Dwell Time at Start
Parameter b6-01 determines the frequency that is held for the time set in b6-02 during acceleration.
No.
b6-01
b6-02
n
b6-03, b6-04: Dwell Reference, Dwell Time at Stop
Parameter b6-03 determines the frequency that is held for the time set in b6-04 during deceleration.
No.
b6-03
b6-04
u

b8: Energy Saving

The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient level.
Note:
1. Energy Saving is not designed for applications that experience instantaneous heavy loads or applications that rarely operate with light
load conditions.
2. Energy Saving is designed for applications with variable torque (Normal Duty) and is not appropriate for applications where the load
may suddenly increase.
3. The performance of the Energy Saving function depends on the accuracy of the motor data. Always perform Auto-Tuning and correctly
enter the motor data before using this function.
n
b8-01: Energy Saving Control Selection
Enables or disables the Energy Saving function.
No.
b8-01
Setting 0: Disabled
Setting 1: Enabled
n
b8-04: Energy Saving Coefficient Value
Determines the level of maximum motor efficiency. Setting range is 0.0 to 2000.0 for drives 3.7 kW and smaller. The display
resolution depends on the rated output power of the drive.
No.
b8-04
Note:
The default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically when
Auto-Tuning for Energy Saving is performed
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
OFF
Run Command
Output Frequency
b6-02
Figure 5.21 Dwell Function at Start and Stop
Name
Dwell Reference at Start
Dwell Time at Start
Name
Dwell Reference at Stop
Dwell Time at Stop
Parameter Name
Energy Saving Control Selection
Name
Energy Saving Coefficient Value
(Refer to Auto-Tuning on page
ON
OFF
b6-01
b6-03
b6-04
Setting Range
0.0 to 400.0 Hz
0.0 to 10.0 s
Setting Range
0.0 to 400.0 Hz
0.0 to 10.0 s
Setting Range
Setting Range
0.00 to 655.00
129).
5.2 b: Application
Default
0.0 Hz
0.0 s
Default
0.0 Hz
0.0 s
Default
0, 1
0
Default
Determined by
E2-11, and o2-04