Monitor Data - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

Register No.
Control Selection Setting
bit 0
bit 1
bit 2, 3
bit 4
000FH
bit 5 to B
bit C
bit D
bit E
bit F
0010H to 001AH
Reserved
001BH
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
001DH to 001FH
Reserved
3004H
Set Time – Hours/Minutes (HHmm)
3005H
Set Date – Year/Day of Week (YYdd)
3006H
Set Date – Month/Day (MMDD)
RTC Set Command/Status
0 = Complete
3007H
1 = Set RTC data using registers 3004H to 3006H
8 = failed
RTC Enter
302FH
0 = Overwrite RTC data using registers 3004H to 3006H. Only effective when 3030H bit 1 (RTC Enter Enable) is set.
bit 1
3030H
bit 2
u

Monitor Data

Monitor data can be read only.
Register No.
Drive Status 1
bit 0
bit 1
bit 2
bit 3
bit 4
0020H
bit 5
bit 6
bit 7
bit 8 to bit D
bit E
bit F
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Reserved
PID Setpoint Input
Reserved
PI2 Target Input
Reserved
Enable Terminal S5 Input for Broadcast Data
Enable Terminal S6 Input for Broadcast Data
Enable Terminal S7 Input for Broadcast Data
Enable Terminal S8 Input for Broadcast Data
RTC Enter Enable
RTC TIE Fault Enable
During Run
During Reverse
Drive Ready
Fault
Data Setting Error
Multi-Function Contact Output (terminal M1-M2)
Reserved
ComRef status
ComCtrl status
C.9 MEMOBUS/Modbus Data Table