YASKAWA P1000 Technical Manual page 313

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

Digital Operator Display
Cause
Sequence error
Digital Operator Display
EF0
Cause
An external fault was received from the
PLC with F6-03 set to 3, which allows the
drive to continue running after an external
fault occurs.
There is a problem with the PLC program. Check the PLC program and correct problems.
Digital Operator Display
EF1
EF2
EF3
EF4
EF5
EF6
EF7
EF8
Cause
An external device has tripped an alarm
function.
Wiring is incorrect.
Multi-function contact inputs are set
incorrectly.
Digital Operator Display
EoF
EoF
Cause
The multi-function digital input for
EmergOverrideFWD (H1-oo = AF) has
been closed.
Digital Operator Display
Eor
Eor
Cause
The multi-function digital input for
EmergOverrideREV (H1-oo = B0) has
been closed.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Forward/Reverse Run Command Input Error
EF
Both forward run and reverse run closed simultaneously for longer than 0.5 s.
Check the forward and reverse command sequence and correct the problem.
Note:
When minor fault EF detected, motor ramps to stop.
Option Card External Fault
An external fault condition is present.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
External Fault (Input Terminal S1)
External fault at multi-function input terminal S1.
External fault (input terminal S2)
External fault at multi-function input terminal S2.
External fault (input terminal S3)
External fault at multi-function input terminal S3.
External fault (input terminal S4)
External fault at multi-function input terminal S4.
External fault (input terminal S5)
External fault at multi-function input terminal S5.
External fault (input terminal S6)
External fault at multi-function input terminal S6.
External fault (input terminal S7)
External fault at multi-function input terminal S7.
External fault (input terminal S8)
External fault at multi-function input terminal S8.
Remove the cause of the external fault and reset the multi-function input value.
• Ensure the signal lines have been connected properly to the terminals assigned for external fault detection
(H1-oo = 2C to 2F).
• Reconnect the signal line.
• Check if the unused terminals have been set for H1-oo = 2C to 2F (External Fault).
• Change the terminal settings.
Emergency Override Forward Run
Open H1-oo = AF if the emergency condition is no longer present
Emergency Override Reverse Run
Open H1-oo = B0 if the emergency condition is no longer present
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
6.5 Alarm Detection