Setting 0: Standard
Setting 1: EZ Sleep/Wake-up
n
b5-90: EZ Sleep Unit
Sets the unit, range, and resolution of parameters b5-91 and b5-92.
No.
b5-90
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
Setting 0: Hz
Setting 1: RPM (number of motor poles must be entered)
n
b5-91: EZ Minimum Speed
Sets the PID minimum speed and integral lower limit.
The lower limit of the internal value is the higher of b5-34 and d2-02.
No.
b5-91
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-92: EZ Sleep Level
When the drive output frequency (or speed) is at or below this level for the time set in b5-93, the drive will go to sleep.
The internal lower limit of this parameter is b5-91 (EZ Min Speed) + 1 Hz.
No.
b5-92
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-93: EZ Sleep Time
The drive will go to sleep when the drive output frequency is at or below the level set to b5-92 for the time set in this parameter.
No.
b5-93
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-94: EZ Wake-up Level
If b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below this level for the time
set in b5-96. For reverse-acting, the PID Feedback has to be above this level for the time set in b5-96.
If b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below the PID Setpoint
minus this level (for normal acting PID) for the time set in b5-96. For reverse-acting, Wake-up level is PID Setpoint plus this
level. The PID Feedback has to be above the wake-up level for the time set in b5-96.
No.
b5-94
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-95: EZ Wake-up Mode
Sets how the wake-up level is determined.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Name
EZ Sleep Unit
Name
EZ Minimum Speed
Name
EZ Sleep Level
Name
EZ Sleep Tim
Name
EZ Wake-up Level
5.2 b: Application
Setting Range
<1>
0, 1
Setting Range
<1>
0.0 to 400.0 Hz
or 0 to 24000 RPM
Setting Range
<1>
0.0 to 400.0 Hz
or 0 to 24000 RPM
Setting Range
<1>
0.0 to 10000.0
Setting Range
<1>
0.00 to 600.00%
Default
0
Default
0.0
Default
0.0
Default
5.0 s
5
Default
0.00
171