3.8 Main Circuit Wiring
Drive Model
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
U/T1, V/T2, W/T3
4A0930
⊖, ⊕1
⊕3
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
U/T1, V/T2, W/T3
4A1200
⊖, ⊕1
⊕3
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2> Install a GFCI or use 10 mm
When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. For
Note:
more information, contact Yaskawa or your nearest sales representative.
n
Three-Phase 600 V Class
Drive Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0003
⊖, ⊕1, ⊕2
5A0004
5A0006
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0009
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0011
B1, B2
90
Recomm. Gauge
Terminal
2
(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.
Table 3.5 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Recomm. Gauge
Terminal
mm
Wire Range
AWG, kcmil
AWG, kcmil
4/0 × 4P×2
4/0 × 4P×2
–
–
3/0
300 × 4P×2
300 × 4P×2
–
–
4/0
Wire Range
2
2
(AWG, kcmil)
mm
(AWG, kcmil)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5 to 6.0
–
(14 to 10)
2.5 to 6.0
–
(14 to 10)
6.0
2.5 to 6.0
(10)
(14 to 10)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5 to 6.0
–
(14 to 10)
2.5 to 6.0
–
(14 to 10)
6.0
4.0 to 6.0
(10)
(12 to 10)
6.0
2.5 to 16
(10)
2.5
2.5 to 16
(14)
2.5 to 16
–
2.5 to 6.0
–
(14 to 10)
10
4.0 to 6.0
(8)
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Screw
Size
3/0 to 300
3/0 to 300
M12
4/0 to 300
4/0 to 300
3/0 to 250
4/0 to 300
4/0 to 300
M12
250 to 300
4/0 to 300
4/0 to 250
Screw
Size
M4
M4
(14 to 6)
(14 to 6)
M4
(14 to 6)
M5
(12 to 8)
Tightening Torque
N·m (lb.in.)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
Tightening Torque
N·m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
2.1 to 2.3
(18.6 to 20.4)
2.0 to 2.5