5.10 o: Operator Related Settings
No.
Frequency Reference and Frequency Related Monitor Custom Units
o1-14
u

o2: Digital Operator Keypad Functions

These parameters determine the functions assigned to the operator keys.
n
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Determines whether the LO/RE key on the digital operator will be enabled for switching between LOCAL and REMOTE.
No.
o2-01
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is
selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07.
o2-01
b1-07
0
1
n
o2-02: STOP Key Function Selection
Determines if the STOP key on the digital operator will stop drive operation when the drive is controlled from a remote source
(i.e., not from digital operator).
No.
o2-02
Setting 0: Disabled
Setting 1: Enabled
The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle
the Run command to restart the drive if the drive has been stopped by pressing the STOP key.
n
o2-03: User Parameter Default Value
After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,
parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters
to the user-set default values.
No.
o2-03
Setting 0: No Change (Awaiting Command)
Setting 1: Set User Initialize Values
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
270
Name
3
Name
LO/RE Key Function Selection
Table 5.36 LO/RE Key and b1-07
Switch from LOCAL to REMOTE
0
Not possible
1
Not possible
Will not run until a new Run command is
0
entered.
If a Run command is entered, the drive will start
1
running as soon as the LO/RE key is pushed to
change from LOCAL to REMOTE.
Name
STOP Key Function Selection
Refer to A1-03: Initialize Parameters on page 143
Name
User Parameter Default Value
Setting Range
Setting Range
Table 5.36
lists the setting combinations for o2-01 and b1-07.
Switch from REMOTE to LOCAL
Not possible
Not possible
Run not possible
Run not possible
Setting Range
for details on drive initialization.
Setting Range
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
30 to 7A
Default
0, 1
Default
0, 1
Default
0 to 2
41
1
1
0