YASKAWA P1000 Technical Manual page 449

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
F6-08
Reset Communication
(36A)
Parameters
<2>
F6-10
CC-Link Node Address
(3B6)
F6-11
CC-Link Communication
(3B7)
Speed
F6-14
bUS Error Auto Reset
(3BB)
F6-20
MECHATROLINK Station
(36B)
Address
F6-21
MECHATROLINK Frame
(36C)
Size
F6-22
MECHATROLINK Link
(36D)
Speed
F6-23
MECHATROLINK
(36E)
Monitor Selection (E)
F6-24
MECHATROLINK
(36F)
Monitor Selection (F)
F6-25
Operation Selection at
(3C9)
Watchdog Timer Error (E5)
F6-26
MECHATROLINK bUS
(3CA)
Errors Detected
F6-30
PROFIBUS-DP Node
(3CB)
Address
F6-31
PROFIBUS-DP Clear Mode
(3CC)
Selection
F6-32
PROFIBUS-DP Data
(3CD)
Format Selection
F6-35
CANopen Node ID
(3D0)
Selection
F6-36
CANopen Communication
(3D1)
Speed
F6-41
CompoNet Communication
(03D6)
Speed
<1>
F6-50
DeviceNet MAC Address
(3C1)
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Description
0: Communication-related parameters (F6-oo/F7-oo) are not reset when
the drive is initialized using A1-03.
1: Reset all communication-related parameters
(F6-oo/F7-oo) when the drive is initialized using A1-03.
Sets the node address if a CC-Link option is installed.
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
0: Disabled
1: Enabled
Sets the station address when the MECHATROLINK option has been
installed.
0: 32 byte
1: 17 byte
0: 10 Mbps
1: 4 Mbps
Sets the MECHATROLINK-II monitor (E).
Sets the MECHATROLINK-II monitor (F).
0: Ramp to stop. Decelerate using the deceleration time in C1-02.
1: Coast to stop
2: Fast stop. Decelerate using the deceleration time in C1-09.
3: Alarm only
Sets the number of option communication errors (bUS).
Sets the node address.
0: Resets drive operation with a Clear mode command.
1: Maintains the previous operation state when Clear mode command is given.
0: PPO Type
1: Conventional
<1>
2: PPO (w/bit 0)
<1>
3: PPO Type (Auto Enter)
<1>
4: Conventional (Auto Enter)
<1>
5: PPO (w/bit0, Auto Enter)
Sets the node address.
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
Reserved.
Selects the drive MAC address.
B.7 F: Communication Options
Values
Default: 0
Range: 0, 1
Default: 0
Min.: 0
Max.: 64
Default: 0
Range: 0 to 4
Default: 0
Range: 0, 1
Default: 21
<4>
Min.: 20
Max.: 3F
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
Default: 1
Range: 0 to 3
Default: 2
Min.: 2
Max.: 10
Default: 0
Min.: 0
Max.: 125
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 5
Default: 0
Min.: 0
Max.: 126
Default: 6
Range: 0 to 8
Default: 64
Min.: 0
Max.: 64
Page
200
200
200
201
202
202
202
202
202
B
203
449

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents