5.2 b: Application
Setting 1: 0.01% (100.00%: Maximum Frequency)
The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min (Set the Motor Poles)
The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined (Determined by b5-38 and b5-39)
Parameters b5-38 and b5-39 determine the units based on b5-46 setting.
n
b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID
feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No.
b5-38
b5-39
Setting 0: No decimal places
Setting 1: One decimal place
Setting 2: Two decimal places
Setting 3: Three decimal places
n
b5-46: PID Setpoint Monitor Unit Selection
Sets the digital operator display units in U5-01 and U5-04 when b5-20 is set to 3.
No.
b5-46
Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPN (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)
Setting 15: "Hg (Inches of Mercury)
Setting 25: None
n
b5-89: Sleep Method Selection
Determines how the drive sleeps and wakes-up when using PID.
No.
b5-89
170
Name
PID Setpoint User Display
PID Setpoint Display Digits
Name
PI Setpoint Monitor Unit Selection
Name
Sleep Method Selection
Setting Range
1 to 60000
0 to 3
Setting Range
0 to 15; 25
Setting Range
0, 1
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
10000
2
Default
0
Default
0