Devicenet Parameters - YASKAWA P1000 Technical Manual

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

Setting 0: Auto detection
Setting 1: 10 kbps
Setting 2: 20 kbps
Setting 3: 50 kbps
Setting 4: 125 kbps
Setting 5: 250 kbps
Setting 6: 500 kbps
Setting 7: 800 kbps
Setting 8: 1 Mbps
u

DeviceNet Parameters

Parameters F6-50 through F6-63 set the drive to operate on a DeviceNet network.
n
F6-50: DeviceNet MAC Address
Sets the MAC address for a DeviceNet option card.
No.
F6-50
n
F6-51: DeviceNet Communication Speed
Sets the communication speed for a DeviceNet option card.
To assign the baud rate for the drive from the upper controller, set F6-51 = 3.
To make the drive detect the network speed, set F6-51 = 4. The drive will automatically adjust itself after detecting the network
speed.
No.
F6-51
Setting 0: 125 kbps
Setting 1: 250 kbps
Setting 2: 500 kbps
Setting 3: Adjustable from network
Setting 4: Auto detection
n
F6-52: DeviceNet PCA Setting
Defines the format for data the drive receives from the DeviceNet master.
No.
F6-52
n
F6-53: DeviceNet PPA Setting
Defines the format for data sent from the drive to the DeviceNet master.
No.
F6-53
n
F6-54: DeviceNet Idle Mode Fault Detection
Determines whether the drive triggers an EF0 fault when no data is received from the master (e.g., when the master is idling).
No.
F6-54
Setting 0: Enabled
Setting 1: Disabled, No Fault Detection
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Parameter Name
DeviceNet MAC Address
Parameter Name
DeviceNet Communication Speed
Parameter Name
DeviceNet PCA Setting
Parameter Name
DeviceNet PPA Setting
Parameter Name
DeviceNet Idle Mode Fault Detection
5.6 F: Option Settings
Setting Range
0 to 64
Setting Range
0 to 4
Setting Range
0 to 255
Setting Range
0 to 255
Setting Range
0 to 4
Default
64
Default
4
Default
21
5
Default
71
Default
0
203

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents