H5-11: Communications Enter Function Selection
Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications.
to Enter Command on page
No.
H5-11
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
n
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No.
H5-12
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1 will
start and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
536.
Name
Communications Enter Function Selection
Name
Run Command Method Selection
C.4 MEMOBUS/Modbus Setup Parameters
Setting Range
0 or 1
Setting Range
0 or 1
Refer
Default
0
Default
0