C.9 MEMOBUS/Modbus Data Table
Register No.
oFC3x Contents (CN5-C)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
00E5H
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
00E6H to 00FFH
Reserved
<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for
a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor capacity is
higher than 11 kW.
Refer to Power Ratings on page
<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04.
u

Broadcast Messages

Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.
Digital Input Command
bit 0
bit 1
bit 2, 3
bit 4
0001H
bit 5
bit 6 to B
bit C
bit D
bit E
bit F
0002H
Frequency Reference
532
Contents
Comm. ID Error (oFC30)
Model Code Error (oFC31)
Sumcheck Error (oFC32)
Comm. option timeout waiting for response (oFC33)
MEMOBUS Timeout (oFC34)
Drive timeout waiting for response (oFC35)
CI Check Error (oFC36)
Drive timeout waiting for response (oFC37)
Control Command Selection Error (oFC38)
Drive timeout waiting for response (oFC39)
Control Response Selection 1 Error (oFC40)
Drive timeout waiting for response (oFC41)
Control Response Selection 2 Error (oFC42)
Control Response Selection Error (oFC43)
Reserved
394.
Contents
Forward Run (0: Stop 1: Run)
Direction Command (0: Forward, 1: Reverse)
Reserved
External Fault
Fault Reset
Reserved
Multi-Function Digital Input S5
Multi-Function Digital Input S6
Multi-Function Digital Input S7
Multi-Function Digital Input S8
30000/100%