5.2 b: Application
n
b8-05: Power Detection Filter Time
Determines how often in milliseconds the output power is measured. The Energy Saving function continuously searches out
the lowest output voltage to achieve minimum output power.
Reducing this setting increases the response time. If the filter time is too short, the motor may become unstable with a lighter
load.
No.
b8-05
n
b8-06: Search Operation Voltage Limit
Sets the voltage limit for the Speed Search optimal output voltage detection as a percentage of the maximum output voltage.
The drive will keep the output voltage above this level during the search operation to prevent motor stalling.
No.
b8-06
176
Name
Power Detection Filter Time
Name
Search Operation Voltage Limit
Setting Range
0 to 2000 ms
Setting Range
0 to 100%
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default
20 ms
Default
0%