Setting 6: DC Injection Braking Current
The current level used for DC Injection Braking is set as a percentage of the drive rated current.
Setting 7: Torque Detection Level
Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog input.
The analog input replaces the level set to L6-02. An analog input of 100% (10 V or 20 mA) sets a torque detection level equal
to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection level settings are required.
Refer to L6: Torque Detection on page 255
Setting 8: Stall Prevention Level
Allows an analog input signal to adjust the Stall Prevention level.
use the lower value of the Stall Prevention level set to L3-06 or the level coming from the selected analog input terminal.
Setting 9: Output Frequency Lower Limit Level
The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID Feedback
Supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Methods on page
161.
Setting C: PID Setpoint
Supplies the PID setpoint value and makes the frequency reference selected in parameter b1-01 no longer the PID setpoint.
PID operation to be enabled in b5-01 to use this setting.
Setting D: Frequency Bias
The input value of an analog input set to this function will be added to the frequency reference. This function can be used with
any frequency reference source.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
100%
50%
20%
10%
0
5 V
10 V
1V 2V
Figure 5.60 Accel/Decel Time Gain with Analog Input Terminal
DC Injection Braking Current Level
Drive Rated
Figure 5.61 DC Injection Braking Current Using an Analog Input Terminal
for details on torque detection.
Stall Prevention Level during Run
100%
30%
0
Figure 5.62 Stall Prevention During Run Using an Analog Input Terminal
Acceleration/deceleration gain from 1 to 10 V
(10 V)
× 10 (%)
=
Input Voltage (V)
100%
Current
0
10 V
(4)
(20 mA)
Figure 5.62
shows the setting characteristics. The drive will
Analog Input Level
30%
100%
Refer to PID Setpoint Input Methods on page
5.7 H: Terminal Functions
Refer to PID Feedback Input
161.
5
229