B.16 Defaults by Drive Model
No.
o2-04
E2-11
b3-04
V/f Gain during Speed Search
b3-06
Output Current 1 during Speed Search
Output Current 2 during Speed Search
b3-07
(Speed Estimation Type)
b3-26
Start Speed Search Select
b8-03
Energy Saving Control Filter Time Constant
b8-04
Energy Saving Coefficient Value
C5-17
Motor Inertia
C6-02
Carrier Frequency Selection
E2-01
Motor Rated Current
E2-02
Motor Rated Slip
E2-03
Motor No-Load Current
E2-05
Motor Line-to-Line Resistance
E2-06
Motor Leakage Inductance
E2-10
Motor Iron Loss for Torque Compensation
L2-02
Momentary Power Loss Ride-Thru Time
L2-03
Momentary Power Loss Minimum Baseblock Time
L2-04
Momentary Power Loss Voltage Recovery Ramp Time
L3-24
Motor Acceleration Time for Inertia Calculations
L8-02
Overheat Alarm Level
L8-35
Installation Method Selection
L8-38
Carrier Frequency Reduction Selection
n1-03
Hunting Prevention Time Constant
490
Name
Model CIMR-Po
Drive Model Selection
Motor Rated Power
Unit
2A0110
2A0138
Hex.
70
30
kW (HP)
(40)
(50)
%
80
0.5
s
0.50
0.50
46.27
38.16
2
0.220
0.273
kgm
7
A
105
131
Hz
1.8
1.33
A
21.9
38.2
Ω
0.064
0.039
%
20.8
18.8
W
699
823
s
2
s
1.1
s
0.6
s
0.323
0.32
°C
130
130
0
2
ms
10
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Default Settings
2A0169
2A0211
72
73
74
37
45
55
(60)
(75)
80
80
80
0.5
0.5
0.5
0.50
2.00
35.78
31.35
0.333
0.490
7
7
160
190
1.6
1.43
44
45.6
0.03
0.022
20.2
20.5
852
960
2
2
1.1
1.2
1.3
0.6
1
0.387
0.317
130
125
0
0
2
2
10
10
10
7
2
1
0
2

Hide quick links: