5.10 o: Operator Related Settings

5.10 o: Operator Related Settings
These parameters are for controlling the various functions, features, and display of the digital operator.
 o1: Digital Operator Display Selection
These parameters determine how data appears on the operator display.
o1-01: Drive Mode Unit Monitor Selection
If o1-02 is set to 5, any monitors from among the U parameters can be displayed. Use o1-01 to select the monitors.
When using an LED operator, pressing the up arrow key will display the following data: speed reference  rotational
direction  output speed  output current  o1-01 selection. 
Parameter o1-01 lets the user select the content of the last monitor in this sequence. (There is no effect like this on an
LCD operator.)
This is done by entering the 1 part of U1-. Certain monitors are not available in some control modes.
No.
o1-01
<1> U2- and U3- parameters cannot be selected.
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter is displayed upon power up.
monitors.
No.
o1-02
Setting 1: Frequency reference (U1-01)
Setting 2: Motor direction
Setting 3: Output frequency (U1-02)
Setting 4: Output current (U1-03)
Setting 5: User-selected monitor (set by o1-01)
o1-03: Digital Operator Display Selection
Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units, then set
parameters o1-10 and o1-11.
No.
o1-03
Setting 0: 0.01 Hz units
Setting 1: 0.01% units (100% = max. output frequency)
Setting 2: min
-1
units (calculated by the max output frequency and the no. of motor poles)
Setting 3: User-set units (use o1-10, o1-11)
Set the value use for the maximum frequency reference to o1-10. The placement of the decimal point in this number
should be set to o1-11.
For example, to have the maximum output frequency displayed as "100.00", set the o1-10 = 1000 and o1-11 = 2 (i.e.,
1000 with 2 decimal points).
Note: 1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
 U1-01: frequency reference
 U1-02: output frequency
 U1-05: motor speed
 U1-16: output frequency after softstarter (accel/decel ramp generator)
 d1-01 to d1-17: frequency references
2. Setting o1-03 to 2 requires that the number of motor poles be entered to E2-04, E4-04, and E5-04.
314
Name
Drive Mode Unit Monitor Selection
Name
User Monitor Selection after Power Up
Name
Digital Operator Display Selection
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Setting Range
104 to 813
U1-04 (Control Mode) to U8-13
(DWEZ Version Control Monitor 3)
Refer to U: Monitor Parameters on page 321
Setting Range
Setting Range
Default
106 (U1-06)
<1>
for a list of
Default
1 to 5
1
Default
0 to 3
Determined by A1-02