A.4 Drive Derating Data
The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u

Single-Phase Derating

P1000 drives are compatible for use with both three-phase and single-phase input power supplies. The drive output to the
motor is always three-phase, regardless of number of input phases.
Output capacity to the motor is derated when using single-phase input power and the drive firmware includes protection for
single-phase input applications. This protection is enabled by default. Disabling this protection for single-phase input
applications can void warranty and result in premature failure.
Selection of larger models always results in greater output capacity to the motor when supplying the drive with three-phase
input power. However, the selection of larger models does not always yield greater output capacity when using the drive with
single-phase input power.
Several factors affect the amount of derated drive output capacity when single-phase input power is supplied to the drive, such
as:
• single-phase input voltage level
• motor voltage rating
• amount of input impedance.
The tables in this section assist in model selection by considering factors that affect the amount of derating in single-phase
input power applications.
n
Single-Phase Input Sizing (Continuous Full Power)
The Output Capacity Motor FLA listed in the tables allows for a 120% overload for 60 seconds. Contact Yaskawa if assistance
is needed in selecting drive models for heavy duty/single-phase applications with higher overload requirements.
Note:
Adding more impedance than is specified will degrade performance.
Service Factor
When using a service factor greater than 1.15, multiply the nominal power (HP) by the service factor (SF), then select a drive
with a higher power rating than the product of that equation.
Example: 1.5 HP x 1.3 SF = 1.95 SF HP
The user should select a 2 HP or larger drive.
Table A.13 240 V Single-Phase Input (-5% to +10%), 230 V Three-Phase Motor
Without Additional Impedance
Drive Model
Motor Power
(HP)
2A0004
1/3
2A0006
3/4
2A0008
1
2A0010
1
2A0012
1.5
2A0018
2
2A0021
2
2A0030
3
2A0040
3
2A0056
5
2A0069
7.5
2A0081
10
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Yaskawa Reactor Part Number
Drive Input
DC Type
Current (A)
4.3
URX000043
7.7
URX000043
9.5
05P00620-0113
9.5
05P00620-0113
13.7
URX000048
19
05P00620-0120
19
05P00620-0120
27
05P00620-0120
27
05P00620-0124
43
URX000059
62
URX000063
79
URX000072
With Additional Impedance
(use either DC type or AC type)
AC Type
URX000303
URX000303
URX000307
URX000311
URX000316
URX000319
URX000323
URX000323
URX000323
URX000326
URX000332
URX000338
A.4 Drive Derating Data
Motor Power
Drive Input
(HP)
Current (A)
1/2
4.1
3/4
5.7
1
7.2
1
7.8
2
13
3
19
3
19
3
19
5
30
7.5
42
10
56
15
84