YASKAWA P1000 Technical Manual page 283

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

<2> Unit is determined by S3-04.
n
S3-06: Secondary PI Proportional Gain Setting
Sets the proportional gain of the secondary PI controller. A setting of 0.00 disables P control.
No.
S3-06
n
S3-07: Secondary PI Integral Time Setting
Sets the integral time for the secondary PI controller. A setting of 0.0s disables integral control.
No.
S3-07
n
S3-08: Secondary PI Integral Limit Setting
Sets the maximum output possible from the integrator.
No.
S3-08
n
S3-09: Secondary PI Output Upper Limit
Sets the maximum output possible from the secondary PI controller.
No.
S3-09
n
S3-10: Secondary PI Output Lower Limit
Sets the minimum output possible from the secondary PI controller.
No.
S3-10
n
S3-11: Secondary PI Output Level Selection
Sets the secondary PI controller output direction.
No.
S3-11
Setting 0: Normal Output (Direct Acting)
Setting 1: Reverse Output (Reverse Acting)
n
S3-12: Secondary PI Disable Mode
Selects the secondary PI controller output when disabled.
No.
S3-12
Setting 0: No Output (0%)
Setting 1: Lower Limit (S3-10)
Setting 2: Setpoint
n
S3-13: Secondary PI Low Feedback Detection Level
Sets the secondary PI low feedback detection level.
No.
S3-13
<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Name
Secondary PI Proportional Gain Setting
Name
Secondary PI Integral Time Setting
Name
Secondary PI Integral Limit Setting
Name
Secondary PI Output Upper Limit
Name
Secondary PI Output Lower Limit
Name
Secondary PI Output Level Selection
Name
Secondary PI Disable Mode
Name
Secondary PI Low Feedback Detection Level
5.11 S: Special Application
Setting Range
0.00 to 25.00
Setting Range
0.0 to 360.0 s
Setting Range
0.0 to 100.0%
Setting Range
0 to 100.0%
Setting Range
-100.00 to 100.00
Setting Range
0 or 1
Setting Range
0 to 2
Setting Range
<1>
0.00 to 600.00
Default
1.00
Default
1.0 s
Default
100.0%
Default
100.0%
Default
0.00%
Default
0
5
Default
0
Default
<2>
0.00
283

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents