No.
(Addr.
Name
Hex)
F6-79
(0B24)
Baud Rate Select
<3>
F7-01
(3E5)
IP Address 1
<5>
F7-02
(3E6)
IP Address 2
<5>
F7-03
(3E7)
IP Address 3
<5>
F7-04
(3E8)
IP Address 4
<5>
F7-05
Subnet Mask 1
(3E9)
F7-06
Subnet Mask 2
(3EA)
F7-07
Subnet Mask 3
(3EB)
F7-08
Subnet Mask 4
(3EC)
F7-09
Gateway Address 1
(3ED)
F7-10
Gateway Address 2
(3EE)
F7-11
Gateway Address 3
(3EF)
F7-12
Gateway Address 4
(3E0)
F7-13
Address Mode at Startup
(3F1)
F7-14
Duplex Mode Selection
(3F2)
F7-15
Communication Speed
(3F3)
Selection
F7-16
Communication Loss
(3F4)
Timeout
F7-17
EtherNet/IP Speed Scaling
(3F5)
Factor
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Description
Sets the baud rate for the P1 protocol.
2: 4800
3: 9600
Sets the most significant octet of network static IP address.
Sets the second most significant octet of network static IP address.
Sets the third most significant octet of network static IP address.
Sets the fourth most significant octet of network static IP address.
Sets the most significant octet of network static Subnet Mask.
Sets the second most significant octet of network static Subnet Mask.
Sets the third most significant octet of network static Subnet Mask.
Sets the fourth most significant octet of network static Subnet Mask.
Sets the most significant octet of network Gateway address.
Sets the second most significant octet of network Gateway address.
Sets the third most significant octet of network Gateway address.
Sets the fourth most significant octet of network Gateway address.
Select the option address setting method
<6>
0: Static
1: BOOTP
2: DHCP
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half duplex forced (port 1)/Auto-negotiate duplex mode and
<1>
communication speed (port 2)
4: Half duplex forced (port 1)/Full duplex forced (port 2)
5: Auto-negotiate duplex mode and communication speed (port 1)/Half duplex
<1>
forced (port 2)
6: Auto-negotiate duplex mode and communication speed (port 1)/Full duplex
<1>
forced (port 2)
7: Full duplex forced (port 1)/Half duplex forced (port 2)
8: Full duplex forced (port 1)/Auto-negotiate duplex mode and communication
<1>
speed (port 2)
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
101: 10 Mbps (port 1)/100 Mbps (port 2)
102: 100 Mbps (port 1)/10 Mbps (port 2)
Sets the timeout value for communication loss detection in tenths of a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.
B.7 F: Communication Options
<1>
<1>
<1>
<1>
Values
Page
Default: 3
Range: 2, 3
Default: 192
Range: 0 to 255
Default: 168
Range: 0 to 255
Default: 1
Range: 0 to 255
Default: 20
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 0
Range: 0 to 255
Default: 192
Range: 0 to 255
Default: 168
Range: 0 to 255
Default: 1
Range: 0 to 255
Default: 1
Range: 0 to 255
Default: 2
Range: 0 to 2
Default: 1
Range: 0 to 8
Default: 10
Range: 10 to 102
Default: 0.0 s
Min.: 0.0
Max.: 30.0
Default: 0
Min.: -15
Max.: 15