4.8 No-Load Operation Test Run

4.8

No-Load Operation Test Run

u
No-Load Operation Test Run
This section explains how to operate the drive with the motor decoupled from the load during a test run.
n
Before Starting the Motor
Check the following items before operation:
• Ensure the area around the motor is safe.
• Ensure external emergency stop circuitry is working properly and other safety precautions have been taken.
n
During Operation
Check the following items during operation:
• The motor should rotate smoothly (i.e., no abnormal noise or oscillation).
• The motor should accelerate and decelerate smoothly.
n
No-Load Operation Instructions
The following example illustrates a test run procedure using the digital operator.
Note:
Before starting the motor, set the frequency reference d1-01 to 6 Hz.
1.
Turn on the power to the drive. The initial display appears.
2.
Press
to select LOCAL. The LO/RE light will turn on.
Press
to give the drive a Run command. RUN will light and the motor will rotate
3.
at 6 Hz.
4.
Ensure the motor is rotating in the correct direction and that no faults or alarms occur.
If there is no error in step 4, press
frequency in increments of 10 Hz, verifying smooth operation at all speeds. For each
5.
frequency, check the drive output current using monitor U1-03. The current should be well
below the motor rated current.
134
Step
to increase the frequency reference. Increase the
Display/Result
Off
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00 A
LREF
JOG
FWD
FWD/REV
ALARM
DIGITAL OPERATOR JVOP-180
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00 A
LREF
JOG
FWD
FWD/REV
F1
F2
LO
ESC
RE
RESET
ENTER
RUN
STOP
Off
On
ALARM
DIGITAL OPERATOR JVOP-180
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 6.00Hz
U1-02= 0.00Hz
LSEQ
U1-03= 0.00 A
LREF
JOG
FWD
FWD/REV
F1
F2
LO
ESC
RE
RESET
ENTER
RUN
STOP
RUN
RUN
On
Motor
Forward