5.10 o: Digital Operator Related Settings

These parameters concern the various functions and features of the operator.

o1: Display Settings and Selections

u
There parameters determine how data is displayed on the operator screen.
o1-01: Drive Mode Unit Monitor Selection
n
Selects which monitor will be displayed in the operation menu upon power-up when o1-02 = 4. Press the up arrow key four times and select the desired
monitor.
No.
o1-01
Drive Mode Unit Monitor Selection
*U2-
and U3-
parameters cannot be selected.
Detailed Description
To select a monitor, set the three numeric digits that make up that monitor, in other words, enter the o-oo part of Uo-oo. For more information,
Refer to U1: Status Monitors on page
The following example explains how to set U4-03 (Cooling Fan Operation Time) to be displayed when the drive is first powered up.
1.
Power up the drive.
2.
Press the
key until the parameter settings screen appears.
3.
Press
to enter the parameter settings menu.
4.
Scroll to o1-01 by pressing
5.
Press
and
to set "403".
6.
Press
to save the setting.
7.
The screen display will automatically return to step 4.
8.
Press
until the display returns to the first screen.
o1-02: User Monitor Selection After Power Up
n
Selects which monitor will be displayed upon power-up. Defaulted to show the frequency reference when the drive is first turned on.
No.
Parameter Name
o1-02
User Monitor Selection After Power Up
o1-03: Digital Operator Display Selection
n
Parameter o1-03 allows the programmer to change the units used in the speed monitors and when some speed parameters are displayed.
No.
Parameter Name
o1-03
Digital Operator Display Selection
The o1-03 parameter will change the units of the following parameters along with o1-10 and o1-11.
No.
U1-01
U1-02
U1-05
U1-16
d1-01 to d1-17
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Parameter Name
215.
Step
and
.
1: Frequency Reference (U1-01)
2: Forward/Reverse
3: Output Frequency (U1-02)
4: Output Current (U1-03)
5: User Monitor (set by o1-01)
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (enter the number of motor poles)
3: User-set

5.10 o: Digital Operator Related Settings

Setting Range
*
104 to 621 (U1-04 to U6-21
)
Setting Range
Setting Range
Parameter Name
Frequency Reference
Output Frequency
Motor Speed
Output Frequency after Soft Start
Frequency Reference 1 to 17
Default
106 (U1-06)
Display/Result
Default
1
Default
0
205
5