YASKAWA P1000 Technical Manual page 524

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

C.9 MEMOBUS/Modbus Data Table
Register No.
002EH
Reserved
002FH
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H
Reserved
0031H
DC Bus Voltage, 1 Vdc units
0032H to 0033H
Reserved
0034H
Product Code 1 [ASCII], Product Type
0035H
Product Code 2 [ASCII], Region Code
0036H, 0037H
Reserved
0038H
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H
PID Input, 0.1% units, signed, 100% / max. output frequency
003AH
PID Output, 0.1% units, signed, 100% / max. output frequency
003BH, 003CH
Reserved
Communications Error Contents
bit 0
bit 1
bit 2
003DH
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
003EH
Output Frequency
003FH
0040H to 004AH
Used for various monitors U1-oo.
Drive status (U1-12)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
004BH
bit 6
bit 7
bit 8
bit 9
bit A to B
bit E
bit F
Used for various monitors U1-oo, U4-oo, U5-oo and U6-oo.
004CH to 007EH
Fault History on page 482
007FH
Alarm Code,
Used for monitors U2-oo, U3-oo.
0080H to 0097H
Contents on page 533
0098H
High Word of Accumulated Operation Time Monitor, 10 h units (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor, 1 h units (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
00ACH to 00AFH
Reserved
524
<3>
CRC Error
Data Length Error
Reserved
Parity Error
Overrun Error
Framing Error
Timeout
Reserved
<4>
r/min
0.01% units
Refer to U: Monitors on page 479
During Run
During Zero Speed
During Reverse Run
During Fault Reset Signal Input
During Speed Agree
Drive Ready
Alarm
Fault
During Operation Error (oPEoo)
During Momentary Power Loss
Reserved
ComRef status, NetRef status
ComCtrl status, NetCtrl status
for parameter details.
Refer to Alarm Register Contents on page 535
Refer to U: Monitors on page 479
for register value descriptions.
<2>
Contents
for parameter details.
Refer to U2: Fault Trace on page 481
for alarm codes.
for parameter details and
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
and
Refer to U3:
Refer to Fault Trace