YASKAWA P1000 Technical Manual page 207

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

Setting 2: External Reference 1/2 Selection
This function switches the Run command and frequency reference source between External reference 1 and 2 if the drive is
in the REMOTE mode.
Status
Open
External reference 1 is used (defined by parameters b1-01 and b1-02)
Closed
External reference 2 is used (defined by parameters b1-15 and b1-16)
Note:
Default drive settings do not allow switching between External reference 1 and 2 during run.
Selection on page 151
Setting 3 to 5: Multi-Step Speed Reference 1 to 3
Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs.
182
for details.
Setting 6: Jog Reference Selection
The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.
Frequency Reference on page 182
Setting 7: Accel/Decel Time Selection 1
Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04).
Times 1 and 2 on page 177
Setting 8, 9: Baseblock Command (N.O., N.C.)
When the drive receives a baseblock command, the output transistors stop switching, the motor coasts to stop, and a bb alarm
flashes on the digital operator to indicate baseblock. When baseblock ends while a Run command is active, the drive performs
Speed Search to restart the motor.
Digital Input Function
Setting 8 (N.O.)
Setting 9 (N.C.)
WARNING! Sudden Movement Hazard. When using a mechanical holding brake with the drive in a lifting application, close the brake when
the drive output is cut off by a baseblock command triggered by one of the input terminals. Failure to comply will result in a slipping load
from the motor suddenly coasting when the baseblock command is entered and may cause serious injury or death.
Setting A: Accel/Decel Ramp Hold
When the digital input programmed for the Accel/decel ramp hold function closes, the drive locks (holds) the output frequency.
Acceleration or deceleration resumes when the input is reopened.
If the Accel/decel ramp hold function is enabled (d4-01 = 1), the drive saves the output frequency to memory when the Ramp
Hold input is closed. When the drive is restarted after stop or after power supply interruption, the saved output frequency
becomes the frequency reference (provided that the Accel/decel ramp hold input is still closed).
Reference Hold Function Selection on page 186
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
if this feature is required by the application.
for details.
for details.
Normal operation
Baseblock (Interrupt output)
OFF
ON
Run command
Baseblock input
Frequency
reference
Output frequency
Figure 5.38 Baseblock Operation During Run
for details.
Description
Refer to d1: Frequency Reference on page
Drive Operation
Input Open
Baseblock
ON
release
Begin Speed Search from the
previous frequency reference
Output off, motor coasts
5.7 H: Terminal Functions
Refer to b1-07: LOCAL/REMOTE Run
Refer to d1:
Refer to C1-01 to C1-04: Accel, Decel
Input Closed
Baseblock (Interrupt output)
Normal operation
Refer to d4-01: Frequency
5
207