YASKAWA P1000 Technical Manual page 151

Models: 200 v class: 3/4 to 175 hp nd 400 v class: 3/4 to 1000 hp nd 600 v class: 1 to 250 hp nd
Hide thumbs Also See for P1000:
Table of Contents

Advertisement

n
b1-04: Reverse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No.
b1-04
Setting 0: Reverse operation enabled
Possible to operate the motor in both forward and reverse directions.
Setting 1: Reverse operation disabled
Drive disregards a Reverse run command or a negative frequency reference.
n
b1-07: LOCAL/REMOTE Run Selection
The drive has three separate control sources that can be switched using digital inputs (H1-oo = 1 (LOCAL/REMOTE
Selection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator.
Selection on page
206,
Refer to Setting 2: External Reference 1/2 Selection on page 207
(LOCAL/REMOTE) Key Function Selection on page 270
• LOCAL: Digital operator. The digital operator sets the frequency reference and Run command.
• REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.
• REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.
When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run command
may already be present at the location at which the source is being switched. In this case, use parameter b1-07 to determine
how the Run command is treated.
No.
b1-07
Setting 0: Run command must be cycled
When the Run command source differs between the old source and the new source (e.g., the old source was the terminals and
the new source is serial communication), and the Run command is active at the new source as the switchover occurs, the drive
will not start or the drive will stop operation if it was previously running. The Run command must be cycled at the new source
to restart the drive.
Setting 1: Accept Run command at the new source
When the Run command is active at the new source, the drive starts or continues operation if it was previously running.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel
from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
n
b1-08: Run Command Selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being used
to adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode).
If required by the application, set b1-08 to allow the drive to run while in Programming Mode.
No.
b1-08
Run Command Selection while in Programming Mode
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Run wait time t
Active deceleration time
Momentary Power Loss
Minimum Baseblock
Time (L2-03)
Min output
frequency
Figure 5.7 Run Wait Time Depending on Output Frequency
Parameter Name
Reverse Operation Selection
Parameter Name
LOCAL/REMOTE Run Selection
Parameter Name
Output frequency
(Max output
when Stop command
was entered
Setting Range
Refer to Setting 1: LOCAL/REMOTE
for details.
Setting Range
Setting Range
5.2 b: Application
100%
frequency)
Default
0, 1
and
Refer to o2-01: LO/RE
Default
0, 1
Default
0 to 2
0
0
5
0
151