H5: Memobus/Modbus Serial Communication - YASKAWA Z1000 User Manual

Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

B.7 H Parameters: Multi-Function Terminals
No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-07
Output Terminal FM
(423)
Signal Level Selection
Multi-Function Analog
H4-08
Output Terminal AM
(424)
Signal Level Selection
u

H5: MEMOBUS/Modbus Serial Communication

No.
(Addr.
Name
Hex)
H5-01
(425)
Drive Slave Address
<1>
H5-02
Communication Speed
(426)
Selection
H5-03
Communication Parity
(427)
Selection
Stopping Method after
H5-04
Communication Error
(428)
(CE)
H5-05
Communication Fault
(429)
Detection Selection
H5-06
Drive Transmit Wait
(42A)
Time
H5-07
RTS Control Selection
(42B)
H5-08
Communication
(62D)
Protocol Selection
H5-09
CE Detection Time
(435)
Unit Selection for
H5-10
MEMOBUS/Modbus
(436)
Register 0025H
Communications
H5-11
ENTER Function
(43C)
Selection
H5-12
Run Command Method
(43D)
Selection
310
LCD Display
Level Select1
0: 0 to 10 V
0: 0-10 VDC
2: 4 to 20 mA
2: 4-20 mA
AO Level Select2
0: 0 to 10 V
0: 0-10 VDC
2: 4 to 20 mA
2: 4-20 mA
LCD Display
Selects drive station slave number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
Serial Comm Adr
to take effect.
Serial Baud Rate
0: 1200 bps
0: 1200 bps
1: 2400 bps
1: 2400 bps
2: 4800 bps
2: 4800 bps
3: 9600 bps
3: 9600 bps
4: 19200 bps
4: 19.2 kbps
5: 38400 bps
5: 38.4 kbps
6: 57600 bps
6: 57.6 kbps
7: 76800 bps
7: 76.8 kbps
8: 115200 bps
8: 115.2 kbps
Cycle power for the setting to take effect.
Serial Com Sel
0: No parity
0: No parity
1: Even parity
1: Even parity
2: Odd parity
2: Odd parity
Cycle power for the setting to take effect.
Serial Fault Sel
0: Ramp to stop
0: Ramp to Stop
1: Coast to stop
1: Coast to Stop
2: Fast Stop
2: Fast-Stop
3: Alarm only
3: Alarm Only
4: Run at d1-04
4: Alarm(d1-04)
0: Disabled
Serial Flt Dtct
1: Enabled
0: Disabled
If communication is lost for more than two seconds, a CE fault
1: Enabled
will occur.
Set the wait time between receiving and sending data.
Transmit WaitTIM
RTS Control Sel
0: Disabled. RTS is always on.
0: Disabled
1: Enabled. RTS turns on only when sending.
1: Enabled
Protocol Select
Selects the communication protocol.
0: MEMOBUS
0: MEMOBUS/Modbus
1: N2
1: N2 (Metasys)
2: P1
2: P1 (APOGEE FLN)
3: BACnet
3: BACnet
Sets the time required to detect a communications error.
CE Detect Time
Adjustment may be needed when networking several drives.
CommReg 25h Unit
0: 0.1 V units
0: 0.1 V
1: 1 V units
1: 1 V
0: Drive requires an Enter command before accepting any
Enter CommandSel
changes to parameter settings.
0: Enter Required
1: Parameter changes are activated immediately without the
1: No EnterRequired
Enter command (same as V7).
Run CommandSel
0: FWD/Stop, REV/Stop
0: FWD Run &REV
1: Run/Stop, FWD/REV
Run
1: Run & FWD/REV
Description
Description
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Values
Page
Default: 0
Range: 0, 2
Default: 0
Range: 0, 2
Values
Page
Default: 1F (Hex)
Min.: 0
178
Max.: FF
Default: 3
178
Range: 0 to 8
Default: 0
179
Range: 0 to 2
Default: 3
179
Range: 0 to 4
Default: 1
179
Range: 0, 1
Default: 5 ms
Min.: 5
179
Max.: 65
Default: 1
180
Range: 0, 1
Default: 0
180
Range: 0 to 3
Default: 2.0 s
Min.: 0.0
180
Max.: 10.0
Default: 0