H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.
Selection on page 71
for details on setting S5.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
u

H5: MEMOBUS/Modbus Serial Communication

Serial communication is possible in the drive using the built-in RS-422/485 port (terminals R+, R-, S+, S-) and programmable
logic controllers (PLCs) or similar devices running the MEMOBUS/Modbus protocol.
The H5-oo parameters set the drive for MEMOBUS/Modbus Communications.
Communication on page 468
u

H6: Pulse Train Input/Output

A one-track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse train
signal can be used as the frequency reference, for PID functions, or as the speed feedback signal in V/f Control.
The pulse output monitor terminal MP can output drive monitor values as a pulse train signal with a maximum frequency of
32 kHz in sinking or sourcing mode.
Use parameters H6-oo to set the scale and other aspects of the pulse input terminal RP and pulse output terminal MP.
n
H6-01: Pulse Train Input Terminal RP Function Selection
Selects the function of pulse train input terminal RP.
No.
H6-01
Pulse Train Input Terminal RP Function Selection
Setting 0: Frequency reference
If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01, b1-15 = 4), the drive
reads the frequency value from terminal RP.
Setting 1: PID feedback value
Using this setting, the feedback value for PID control can be supplied as a pulse signal at terminal RP.
Control on page 141
for details on PID control.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
H4-07, 08 = 0
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor Value
Figure 5.84 Analog Output Gain and Bias Setting Example 3
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
for detailed descriptions of the H5-oo parameters.
Refer to Using the Pulse Train Output on page 69
Name
5.7 H: Terminal Functions
H4-07, 08 = 1
10V
Output Voltage
3 V
-100%
100%
Monitor Value
-4 V
-10 V
Refer to Terminal AM/FM Signal
Setting Range
0 to 2
0 to 2
Refer to MEMOBUS/Modbus Serial
for details.
Setting Range
0 to 3
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
Default
0
0
5
Default
0
Refer to b5: PID
235