H5: Memobus/Modbus Serial Communication; H6: Pulse Train Input/Output - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

5.7 H: Terminal Functions
Figure 5.58
10 V
Output Voltage
5 V
0 V
0%
Example 3: To have an output signal of 3 V at terminal FM when the monitored value is at 0%, set H4-03 to 30%.
Figure 5.59
10 V
Output Voltage
3 V
0 V
0%
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
No.
H4-07
H4-08
Multi-Function Analog Output Terminal AM Signal Level Selection
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA

◆ H5: MEMOBUS/Modbus Serial Communication

Through the drives built in RS-422/RS-485 port (terminals R+, R-, S+, S-), serial communication is possible using
programmable logic controllers (PLCs) or similar devices running the MEMOBUS/Modbus protocol.
The H5- parameters are used to set up the drive for MEMOBUS/Modbus Communications.
Modbus Serial Communication on page 416

◆ H6: Pulse Train Input/Output

A one track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse
train signal can be used as the frequency reference, for PI functions, or as the speed feedback signal in V/f Control.
The pulse output monitor terminal MP can output drive monitor values as a pulse train signal with a maximum frequency
of 32 kHz. It can be used in sinking or sourcing mode.
Use parameters H6- to set the scale and other aspects of the pulse input terminal RP and pulse output terminal MP.
206
H4-07, 08 = 0
100%
Monitor Value
Figure 5.58 Analog Output Gain and Bias Setting Example 1 and 2
H4-07, 08 = 0
100%
Monitor Value
Figure 5.59 Analog Output Gain and Bias Setting Example 3
Name
Multi-Function Analog Output Terminal FM Signal Level Selection
for detailed descriptions of the H5- parameters.
Output Voltage
Gain 150%
Bias 0%
-100%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
Output Voltage
Bias 30%
Gain 100%
-100%
Bias 0%
Gain 100%
Refer to Using the Pulse Train Output on page 87
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
H4-07, 08 = 1
15 V
Gain = 150%
Bias = 0%
10 V
Gain = 100%
Bias = 0%
5 V
Gain = 50%
Bias = 0%
100%
Monitor Value
-5 V
-10 V
-15 V
H4-07, 08 = 1
15 V
Gain = 100%
Bias = 30%
10V
Gain = 100%
Bias = 0%
5 V
100%
Monitor Value
-5 V
-10 V
YEC_common
-15 V
Setting Range
0 to 2
0 to 2
Refer to MEMOBUS/
Default
0
0
for details.