poe-power
output-thresh lower
poe-power
output-thresh upper
C
UPERVISION
OMMANDS
Syntax
poe-power output-thresh lower string
View
System view
Parameter
string: Undervoltage alarm threshold. It ranges from 45.00 V to 47.00 V in the
format of x.x.
Description
Use the poe-power output-thresh lower command to set the undervoltage
alarm threshold of DC output (lower threshold):
For both 220 VAC and 110 VAC input, it is recommended to set the threshold to
45.00 V.
Example
# Set the undervoltage alarm threshold of DC output to 45.00 V.
[SW8800] poe-power output-thresh upper 57.0
Set lower output-threshold power successfully!
Syntax
poe-power output-thresh upper string
View
System view
Parameter
string: Overvoltage alarm threshold. It ranges from 55.00 V to 57.00 V in the
format of X.X.
Description
Use the poe-power output-thresh upper command to set the overvoltage
alarm threshold of DC output (upper threshold):
For both 220 VAC and 110 VAC input, it is recommended to set the threshold to
57.00 V.
Example
# Set the overvoltage alarm threshold of DC output to 57.00V.
[SW8800] poe-power output upper 57.00
Set upper output-threshold power successfully!