8.1 Comparison Output Function

8.1 Comparison Output Function

8.1.1 Overview of Comparison Output Function

● The comparison output function is used for comparing the ""Counter elapsed value by
external input"" or ""Pulse output counter elapsed value of pulse output/PWM output"" to an
arbitrary ""Comparison output setting value"" and outputting the comparison result.
● There are eight points for the comparison result output [CMPx], and the types and channels
of compared counters, and the comparison condition can be arbitrarily allocated by the
software. Also, all comparison output setting values are set to the same counter, and it can
be used as a counter with a maximum of eight steps.
● The conditions of the comparison output are selectable from ""ON when elapsed value is
larger than or equal to setting value"" and ""ON when elapsed value is smaller than setting
value"".
Outline of specifications
Item
No. of comparison
outputs
Comparison object
Comparison
condition
Data range
(Note 1)
I/O numbers vary according to the starting word number of the unit.
8-2
Specifications
Max. 8 points (CMP0 to CMP7: I/O numbers Y0 to Y7)
1)
""Counter elapsed value by external input"" or ""Pulse
output counter elapsed value of pulse output/PWM output""
is compared to an arbitrary setting value.
""ON when elapsed value is smaller than setting
value""/""ON when elapsed value is larger than or equal to
setting value""
-2147483648 to +2147483647
Remarks
(Note
Settable for each point.
Settable for each point.
WUME-FP7MXY-06