Allocation of unit memories: Pulse/PWM status flag
UM number UM0015F
Bit no.
b15-b8
Setting
channel
Monitor
value
H1
Initial value
(Hex)
Monitor values (UM0015F / UM0015E)
Bit no.
b8
b0
b9
b1
b10
b2
b11
b3
b12
b4
b13
b5
b14
b6
b15
b7
(Note 1)
Since Multi I/O Unit Ver.1.1, it is possible to select "ON start" or "OFF start" for starting the pulse
output with the pulse output function. In the Ver.1.0x unit, only "OFF start" is available. (Cannot
change)
Monitor Area
Unit
memory
Name
No. (Hex)
UM 00160
PLS/PWM output
frequency (CH0)
UM 00161
UM 00162
PLS/PWM output
frequency (CH1)
UM 00163
UM 00164
PLS/PWM output
frequency (CH2)
UM 00165
UM 00166
PLS/PWM output
frequency (CH3)
UM 00167
UM 00168
PWM output duty
(CH0)
UM 00169
WUME-FP7MXY-06
b7-b0
PLS3
PWM3
H4
H1
Settings
Functions
Pulse output start logic
Duty error
Duty 0% setting flag
Frequency setting error flag
During pulse output
Frequency setting error flag
During PWM output
Frequency 0Hz setting flag
Flag when setting PWM output
Flag when setting pulse output
Busy flag
Default
H0
H0
13.4 Unit Memory Detailed Information
UM0015E
b15-b8
PLS2
PWM2
H4
H1
Value
1
ON start
(Note 1)
100.1% or more
0
500001 Hz or more
100001 Hz or more
0 Hz
Setting
Setting
During output
Setting range and description
Stores the frequencies of pulse output or
PWM output. They can also be written using
user programs.
(During Pulse output)
Range: 0 to 500,000
Unsigned 32-bit integer
(During PWM output)
Range: 0 to 100,000
Unsigned 32-bit integer
Stores the duty ratios of PWM output. They
can also be written using user programs.
Range: 0 to 1,000 (0.0% to 100.0%)
b7-b0
PLS1
PWM1
H4
H1
0
OFF start
0.0% to 100.0%
Other than 0
Less than 100001 Hz
Less than 100001 Hz
Other than 0 Hz
Unset
Unset
Output Off
PLS0
PWM0
H4
R
W
A
A
A
A
13-37