13.4 Unit Memory Detailed Information
Setting value
HD
HE
HF
Precautions when making settings with programs
● Input voltage should be set in increments of four external input terminals (four groups).
● When the voltage settings of the higher two groups and lower two groups of input voltage are
different, the 5V-24V mode takes priority.
● Input time constant should be set in increments of two external input terminals (eight
groups).
● As the input voltage and input time constant are set for external input terminals, the settings
are effective after the allocation of each function corresponding to inputs X0 to XF.
Input setting (Input time constant high resolution)
Unit
memory
Name
No. (Hex)
Input time
constant setting
UM00070
(X0-X7)
Input time
constant setting
UM00071
(X8-XF)
Allocation of unit memories
UM number UM00071
Bit no.
b15-b12
I/O no.
XF,XE
Input time
constant
Setting
value
H F
Initial value
(Hex)
The value (Hex) of input time constant (for two inputs) is written to the four bits of the unit
memory. When allocating them using the tool software, it is not necessary to write them.
Setting value
H0
H 1
H 2
H 3
H 4
H 5
H 6
13-26
Input voltage
Input time constant effective pulse width
16 µs
2 ms
4 ms
Default
H FFFF
H FFFF
b11-b8
b7-b4
XD,XC
XB,XA
HF
HF
Valid/Invalid
Input time constant effective pulse width
0.5 µs
1.5 µs
32 µs
64 µs
Valid
96 µs
128 µs
256 µs
Setting range and description
Set values indicating input time constant (high
resolution).
UM000070
b3-b0
b15-b12
X9,X8
X7,X6
HF
HF
b11-b8
b7-b4
X5,X4
X3,X2
HF
HF
WUME-FP7MXY-06
R
W
A
A
b3-b0
X1,X0
HF