6.2 Execution Example of Interrupt Function
sequence program until IRET is executed, and the output (Y160) of the 32-point output unit
is output at a high speed.
(For the interrupt occurred at the same time as comparison output)
● The interrupt (INT0) occurs at the same time as the comparison output. The interrupt
program from INT0 of a sequence program until IRET is executed, and the output (Y160) of
the 32-point output unit is output at a high speed.
Configuration
● From the function selection tree, select ""High-speed counter"", allocate high-speed counter
inputs to the inputs (X100-X103), and select ""Direction distinction"".
● From the function selection tree, select ""Comparison match output"", and select ""High-
speed counter CH0"" as a counter to compare the comparison match number CMP0
(external terminal number: Y100).
(For the interrupt occurred when comparison values match)
● From the function selection tree, select ""Interrupt"", and select ""Comparison match output
(When comparison values match)"" from the interrupt conditions in the Interrupt Advanced
settings.
(For the interrupt occurred at the same time as comparison output)
● From the function selection tree, select ""Interrupt"", and select ""Comparison match output
(OFF->ON/ON->OFF)"" from the interrupt conditions.
6-8
WUME-FP7MXY-06