Home position method (Edge detection of home switch)
Moves the current position to the home return direction, and stops at the position where the
leading edge of the first home switch is detected. This coordinate is set as a home position.
Home switch
■
Data set method
Performs the home return based on the home coordinate values in the axis setting area of unit
memories.
● For details of addresses and settings of unit memories, refer to
10.9.3 Settings and Operations of Home Return
● The parameters for home return operations are specified in the "Positioning Parameter
Setting" menu of Configurator PMX.
● When the home return start contact turns on, the pulse output starts and the home return
operation is performed.
● In the following example, the DOG1 method is selected. After the start, it moves at a target
speed and reverses at the time of near home detection. After the redetection of near home
input, it moves at a creep speed until the home position is detected.
WUME-FP7MXY-06
Home return creep speed
Home position (= Current value)
Home return direction
""13.3 List of Unit
10.9 Home Return
Memories"".
10-43