7.4 Elapsed Value Hold Function

7.4 Elapsed Value Hold Function

7.4.1 Overview

● The elapsed value hold function is a function which holds the elapsed value of the counter at
the time of the trigger input signal from an external device.
● The elapsed value hold function is available only for CH0 and CH1. Each elapsed value is
transferred to the hold value areas allocated to each channel.
● It will be valid by turning on the signal (CHx LATCH EN) with a user program.
● The input logics (ON -> OFF edge, and OFF -> ON edge) which enable trigger input signals
can be switched by the signal (CHx TRG LOG).
I/O allocation
Name
CHx IN-A
CHx IN-B
CHx RST
CHx MASK
CHx TRG
CHx LATCH EN
CHx TRG LOG
(Note 1)
The I/O numbers in the table above are for slot number 1 and the starting word number 10. The I/O
numbers actually used vary according to the slot number where the unit is installed and the starting
word number.
Unit memory (UM) allocation
Name
Counter elapsed value area
Counter hold value area
Configuration
When allocating ""High-speed counter"" to the inputs (X100-X107) in the "Multi I/O Unit Setting"
dialog box, check the box for ""Elapsed value hold mode"".
7-12
CH0
CH1
Description
X100
X104
X101
X105
They occupy the counter areas for external inputs (4 points for each
channel).
X102
X106
X103
X107
Y108
X10C
Trigger input signal by an external input.
Y114
Y116
Enables the elapsed value hold function.
Switches the valid condition of trigger input signals.
When this is on, the ON -> OFF edge of the trigger signals (X8, XC) is
Y115
Y117
valid.
When this is off, the OFF -> ON edge of the trigger signals (X8, XC) is
valid.
CH0
UM00110-UM00111
UM00114-UM00115
CH1
UM00112-UM00113
UM00116-UM00117
WUME-FP7MXY-06